Particulars | |
---|---|
Phase |
Three/single |
Frequency, Hz | 50 |
Voltage, V | 415/240 |
Power factor, lag | 0.8 |
Ambient | 40°C |
Altitude | 1000 mtrs |
Speed, rpm | 1500 |
Mounting | Horizontal foot mounted |
Duty | Continuous |
Direction of rotation | Clockwise from DE |
Automatic voltage regulator | M/c mounted |
Voltage regulation | +/-1% with 4% prime mover speed variation |
Standards | IS 4722 -1992, IEC 34 |
Class of insulation | H |
Temperature rise | H |
Enclosure | IP 20 |
Cooling | IC 01 |
Wave form distortion (thd) | Less than 3% |
Overload capacity | 10% overload for 1 hour. once in 12 hours |
Unbalance permitted | 25% with none of the phase currents exceeding the rated current. Temperature rise limits for corresponding class of insulation may exceed 10°C under such conditions. Voltage regulation under above condition will not apply. |
No. of bearings | Single/double |
Lubrication type | Grease lubricated |
Particulars | |
---|---|
Phase | Three/single |
Frequency, Hz | 50 |
Voltage, V | 415/240 |
Power factor, lag | 0.8 |
Ambient | 40°C |
Altitude | 1000 mtrs |
Speed, rpm | 1500 |
Mounting | Horizontal foot mounted |
Duty | Continuous |
Direction of rotation | Clockwise from DE |
Automatic voltage regulator | M/c mounted |
Voltage regulation | +/-1% with 4% prime mover speed variation |
Standards | IS 4722 -1992, IEC 34 |
Class of insulation | H |
Temperature rise | H |
Enclosure | IP 20 |
Cooling | IC 01 |
Wave form distortion (thd) | Less than 3% |
Overload capacity | 10% overload for 1 hour. once in 12 hours |
Unbalance permitted | 25% with none of the phase currents exceeding the rated current. Temperature rise limits for corresponding class of insulation may exceed 10°C under such conditions. Voltage regulation under above conditions will not apply |
No. of bearings | Single/double |
Lubrication type | Grease lubricated |